Condition
- Sage supply sensor detected
- temperatures in excess of 210°F.
Possible Cause
- Heating load at time of error was far below the minimum firing rate of the boiler.
- Defective system circulator or no flow in system piping.
- Improper piping – See boiler piping diagram:
Heat Only / Heat & DHW1 / Heat & DHW2 - Defective boiler circulator, no flow or insufficient flow in boiler loop.
- Control system miswired so that the boiler operation is permitted when no zones are calling.