Soft Lockout 2(A): Boiler Safety Limit Open

Condition

  • Boiler safety limit wired to J6-1, J6-2 or J6-3 are open
  • Condensate trap float switch open
  • Thermal link switch open
  • Burner doos thermostat with manual reset open
  • Air pressure switch contact open
  • Auto reset high limit contact open
  • External High Limits open

Possible Cause

  • Loose wiring to limit device
  • Auto reset limit exceeded. Switch rated at 200f
  • Defective auto reset high limit switch (Open when water temp is below 200f)
  • Plugged condensate trap
  • Thermal link blown due to temperature above 604f – ALP 285 and higher on hear of heat exchanger
  • Burner door manual reset thermostat open due to temperature rise above 500f
  • Air pressure switch contacts open
  • Low Water Cut-Off yellow light on

See possible causes for Hard Lockout 4.

Note: For picture of low voltage circuit board – press page down. To return here press page up botton.