The boiler default is DHW priority. Turn off DHW by reducing the DHW water temp setting on indirect aquastat. Did display change to CH?
Turn off the boiler switch to shut boiler down. After 10 Seconds or more turn the switch back on. Did CH show up on the display?
Remove the thermostat wires and place a jumper between the Heating Tstat terminals on the boiler terminal strip. Did the display show Central Heat (CH)?
Press the status button. Is the “Supply temperature” near or higher than the “Setpoint” water temperture?
Jumper the heating thermostat terminals on the low voltage circuit board. Did the boiler display Central heat?
Bad wire between the boiler and the thermostat. Replace wire.
Are the thermostats wired to a zone panel, zone valves or a single thermostat?
This is normal that the burner is not firing. The temp is satisfied to setpoint temperature
Repair or replace the zone panel.
Check settings on thermostat, change batteries or replace thermostat
Remove the wires from zone panel end switch that connects to the boiler and place them together or meter the end switch for continunity. Does the boiler fire and run?
Jumper the heating t-stat terminals on the boiler low voltage board. Does the boiler display change from standby to central heat?
Repair or replace zone valve
Defective wire, repair or replace
Check for 120Vac from the circulator terminals to the appropriate circ’s. Is 120Vac available at circ terminals?
Is a System circulator wired to the boiler? Usually it would be if the system is zoned with Zone Valves and normally not if zoned with circulators unless there is only one heat zone.
While the boiler is in demand for heat is there 120Vac on the System circulator “L” terminal on the line voltage circuit board?
Replace circulator
replace wire
Call Tech Services
There is a fuse on the line voltage PC board. Check the fuse by removing the fuse and ohm the fuse. Is the fuse blown?
Completed
Turn the boiler off. Disconnect the System and DHW circulator wires to the line voltage circuit board. Replace the fuse. Turn the boiler back on. Did the fuse blow again?
Turn the power off to the boiler and repalce the DHW circulator wires on the board and turn the boiler back on. If the fuse does not blow turn the boiler back off and do the system circ wire. Turn power back on, which connection blew the fuse?
Replace the line voltage circuit board.